Contact
CU/XLPE/STA/PVC 600/1000V N2XBY Cable
N2XBY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 600/1000V, which can be used
· in fixed industrial power applications
· Underground tunnels
· in power and switching stations
· local energy distributions
· industrial plants
Using steel tape armouring offers great mechanical protection, making it rigid with a large radius installation indoors and outdoors.
For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)
Details
Description: N2XBY, XLPE Insulated Copper Power Cable
Conductors: Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.
Insulation: Cross-linked polyethylene XLPE
Insulation Colour: Natural or as required
Filler: Non-hygroscopic Material
Inner Sheath: Polyvinyl Chloride PVC
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
0.6/1kV-3+1 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X4+1X2.5 | 0.7/0.7 | 0.2 | 1.8 | 15.5 | 368 | 4.61/7.41 | 37 | 51 |
3X6+1X4 | 0.7/0.7 | 0.2 | 1.8 | 16.8 | 465 | 3.08/4.61 | 47 | 64 |
3X10+1X6 | 0.7/0.7 | 0.2 | 1.8 | 19.3 | 633 | 1.83/3.08 | 65 | 86 |
3X16+1X10 | 0.7/0.7 | 0.2 | 1.8 | 22.1 | 890 | 1.15/1.83 | 84 | 110 |
3X25+1X16 | 0.9/0.7 | 0.2 | 1.8 | 25.1 | 1272 | 0.727/1.15 | 110 | 140 |
3X35+1X16 | 0.9/0.7 | 0.2 | 1.8 | 26.8 | 1583 | 0.524/1.15 | 135 | 170 |
3X50+1X25 | 1.0/0.9 | 0.2 | 1.9 | 30.2 | 2030 | 0.387/0.727 | 170 | 205 |
3X70+1X35 | 1.1/0.9 | 0.2 | 2.0 | 35.1 | 2810 | 0.268/0.524 | 215 | 250 |
3X95+1X50 | 1.1/1.0 | 0.5 | 2.2 | 40.4 | 4135 | 0.193/0.387 | 265 | 300 |
3X120+1X70 | 1.2/1.1 | 0.5 | 2.3 | 45 | 5135 | 0.153/0.268 | 310 | 345 |
3X150+1X70 | 1.4/1.1 | 0.5 | 2.5 | 49.1 | 6120 | 0.124/0.268 | 350 | 385 |
3X185+1X95 | 1.6/1.1 | 0.5 | 2.8 | 54.3 | 7616 | 0.0991/0.193 | 405 | 435 |
3X240+1X120 | 1.7/1.2 | 0.5 | 2.8 | 59.1 | 9679 | 0.0754/0.153 | 480 | 500 |
3X300+1X150 | 1.8/1.4 | 0.5 | 3.0 | 66 | 11889 | 0.0601/0.124 | 555 | 565 |
0.6/1kV-4+1 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
4X4+1X2.5 | 0.7/0.7 | 0.2 | 1.8 | 16.3 | 434 | 4.61/7.41 | 37 | 51 |
4X6+1X4 | 0.7/0.7 | 0.2 | 1.8 | 17.7 | 549 | 3.08/4.61 | 47 | 64 |
4X10+1X6 | 0.7/0.7 | 0.2 | 1.8 | 20.3 | 759 | 1.83/3.08 | 65 | 86 |
4X16+1X10 | 0.7/0.7 | 0.2 | 1.8 | 24 | 1079 | 1.15/1.83 | 84 | 110 |
4X25+1X16 | 0.9/0.7 | 0.2 | 1.8 | 28.1 | 1557 | 0.727/1.15 | 110 | 140 |
4X35+1X16 | 0.9/0.7 | 0.2 | 1.9 | 29.6 | 1962 | 0.524/1.15 | 135 | 170 |
4X50+1X25 | 1.0/0.9 | 0.2 | 2.0 | 34 | 2601 | 0.387/0.727 | 170 | 205 |
7X70+1X35 | 1.1/0.9 | 0.5 | 2.2 | 40.3 | 3916 | 0.268/0.524 | 215 | 250 |
4X95+1X50 | 1.1/1.0 | 0.5 | 2.3 | 44.8 | 5260 | 0.193/0.387 | 265 | 300 |
4X120+1X70 | 1.2/1.1 | 0.5 | 2.6 | 50.2 | 6545 | 0.153/0.268 | 310 | 345 |
4X150+1X70 | 1.4/1.1 | 0.5 | 2.8 | 54.6 | 7780 | 0.124/0.268 | 350 | 385 |
4X185+1X95 | 1.6/1.1 | 0.5 | 2.9 | 60.5 | 9688 | 0.0991/0.193 | 405 | 435 |
4X240+1X120 | 1.7/1.2 | 0.5 | 3.0 | 67.1 | 12253 | 0.0754/0.153 | 480 | 500 |
4X300+1X150 | 1.8/1.4 | 0.5 | 3.2 | 73.7 | 15078 | 0.0601/0.124 | 555 | 565 |
0.6/1kV-3+2 core copper conductor XLPE insulated PVC sheathed power cable | ||||||||
No. of cores and nominal cross section | Thickness of Insulation | steel tape thickness | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X4+2X2.5 | 0.7/0.7 | 0.2 | 1.8 | 16.6 | 412 | 4.61/7.41 | 37 | 51 |
3X6+2X4 | 0.7/0.7 | 0.2 | 1.8 | 18 | 525 | 3.08/4.61 | 47 | 64 |
3X10+2X6 | 0.7/0.7 | 0.2 | 1.8 | 20.9 | 714 | 1.83/3.08 | 65 | 86 |
3X16+2X10 | 0.7/0.7 | 0.2 | 1.8 | 24 | 1016 | 1.15/1.83 | 84 | 110 |
3X25+2X16 | 0.9/0.7 | 0.2 | 1.8 | 28.1 | 1465 | 0.727/1.15 | 110 | 140 |
3X35+2X16 | 0.9/0.7 | 0.2 | 1.9 | 29.6 | 1769 | 0.524/1.15 | 135 | 170 |
3X50+2X25 | 1.0/0.9 | 0.2 | 2.0 | 34 | 2316 | 0.387/0.727 | 170 | 205 |
3X70+2X35 | 1.1/0.9 | 0.5 | 2.2 | 40.3 | 3230 | 0.268/0.524 | 215 | 250 |
3X95+2X50 | 1.1/1.0 | 0.5 | 2.3 | 44.8 | 4766 | 0.193/0.387 | 265 | 300 |
3X120+2X70 | 1.2/1.1 | 0.5 | 2.5 | 50.2 | 6080 | 0.153/0.268 | 310 | 345 |
3X150+2X70 | 1.4/1.1 | 0.5 | 2.6 | 54.6 | 7005 | 0.124/0.268 | 350 | 385 |
3X185+2X95 | 1.6/1.1 | 0.5 | 2.8 | 60.5 | 8767 | 0.0991/0.193 | 405 | 435 |
3X240+2X120 | 1.7/1.2 | 0.5 | 3.0 | 67.1 | 11105 | 0.0754/0.153 | 480 | 500 |
3X300+2X150 | 1.8/1.4 | 0.5 | 3.2 | 73.7 | 13645 | 0.0601/0.124 | 555 | 565 |